HANDBOOK HVAC FORMULA
RIJOMAC SYSTEM
Controlled Environment Engineering
A.1 KONVERSI AIRFLOW
Dari | Ke | Faktor Konversi |
|---|
1 CFM | 1,699 CMH | × 1,699 |
1 CMH | 0,588 CFM | × 0,588 |
1 m³/s | 3.600 CMH | × 3.600 |
1 m³/s | 2.119 CFM | × 2.119 |
1 L/s | 3,6 CMH | × 3,6 |
1 L/s | 2,119 CFM | × 2,119 |
1 CMH | 0,278 L/s | × 0,278 |
1 CFM | 0,472 L/s | × 0,472 |
A.2 KONVERSI TEKANAN
Dari | Ke | Faktor Konversi |
|---|
1 Pa | 0,102 mmAq | × 0,102 |
1 mmAq | 9,81 Pa | × 9,81 |
1 in.wg | 249 Pa | × 249 |
1 kPa | 1.000 Pa | × 1.000 |
1 bar | 100.000 Pa | × 100.000 |
1 psi | 6.895 Pa | × 6.895 |
1 atm | 101.325 Pa | × 101.325 |
A.3 KONVERSI KAPASITAS PENDINGINAN
Dari | Ke | Faktor Konversi |
|---|
1 TR | 3,517 kW | × 3,517 |
1 kW | 0,284 TR | × 0,284 |
1 TR | 12.000 BTU/h | × 12.000 |
1 kW | 3.412 BTU/h | × 3.412 |
1 BTU/h | 0,000293 kW | × 0,000293 |
A.4 KONVERSI DAYA
Dari | Ke | Faktor Konversi |
|---|
1 HP | 0,746 kW | × 0,746 |
1 kW | 1,341 HP | × 1,341 |
1 HP | 746 Watt | × 746 |
1 kW | 1.000 Watt | × 1.000 |
A.5 KONVERSI SUHU
Konversi | Rumus |
|---|
°C → °F | (°C × 1,8) + 32 |
°F → °C | (°F − 32) ÷ 1,8 |
°C → K | °C + 273,15 |
K → °C | K − 273,15 |
A.6 KONVERSI PANJANG
Dari | Ke | Faktor Konversi |
|---|
1 inch | 25,4 mm | × 25,4 |
1 inch | 0,0254 m | × 0,0254 |
1 ft | 304,8 mm | × 304,8 |
1 ft | 0,3048 m | × 0,3048 |
1 m | 3,281 ft | × 3,281 |
1 m | 39,37 inch | × 39,37 |
A.7 KONVERSI LUAS
Dari | Ke | Faktor Konversi |
|---|
1 m² | 10,764 ft² | × 10,764 |
1 ft² | 0,0929 m² | × 0,0929 |
1 m² | 1.550 in² | × 1.550 |
A.8 KONVERSI VOLUME
Dari | Ke | Faktor Konversi |
|---|
1 m³ | 35,31 ft³ | × 35,31 |
1 ft³ | 0,0283 m³ | × 0,0283 |
1 m³ | 1.000 Liter | × 1.000 |
1 Liter | 0,001 m³ | × 0,001 |
A.9 KONVERSI KECEPATAN UDARA
Dari | Ke | Faktor Konversi |
|---|
1 m/s | 196,85 FPM | × 196,85 |
1 FPM | 0,00508 m/s | × 0,00508 |
1 m/s | 3,6 km/h | × 3,6 |
FPM = Feet Per Minute
A.10 KONVERSI MASSA
Dari | Ke | Faktor Konversi |
|---|
1 kg | 2,205 lb | × 2,205 |
1 lb | 0,454 kg | × 0,454 |
A.11 KONVERSI ENERGI
Dari | Ke | Faktor Konversi |
|---|
1 kWh | 3.600 kJ | × 3.600 |
1 kJ | 0,000278 kWh | × 0,000278 |
1 kWh | 3.412 BTU | × 3.412 |
A.12 QUICK HVAC ENGINEERING REFERENCE
Parameter | Nilai Cepat |
|---|
1 CFM | 1,699 CMH |
1 CMH | 0,588 CFM |
1 m³/s | 3.600 CMH |
1 Pa | 0,102 mmAq |
1 mmAq | 9,81 Pa |
1 TR | 3,517 kW |
1 HP | 0,746 kW |
1 kW | 3.412 BTU/h |
1 m/s | 196,85 FPM |
1 inch | 25,4 mm |
1 m² | 10,764 ft² |
1 m³ | 35,31 ft³ |
Catatan Engineer
Untuk pekerjaan HVAC sehari-hari, tiga konversi yang paling sering digunakan adalah:
Parameter | Konversi Praktis |
|---|
Airflow | 1 CFM = 1,7 CMH |
Cooling Capacity | 1 TR = 3,5 kW |
Tekanan | 10 Pa ≈ 1 mmAq |
Ketiga angka pendekatan tersebut sering digunakan untuk estimasi cepat di lapangan sebelum dilakukan perhitungan detail.